Search
TSI Q-TRAK 7575 Indoor Air Quality Monitor
Available as:
Rental
Key Features
- Simultaneously displays CO2, CO, temperature and humidity measurements
- Calculates dew point, wet bulb and percent outside air
- Large graphic display
- One instrument with multiple plug-in probe options including VOC’s and air velocity
- Store up to 39 days of data collected at one-minute log intervals
- TRAKPRO™ data analysis software provided for data logging, analysis and documenting results
- Bluetooth communications for transferring data or remote polling
- Displays up to 5 measurements
- On-screen messages and instructions
- Supports 12 different languages
Providing a comfortable, safe and healthy indoor environment is an increasingly important concern. Good air quality increases concentration and productivity. It can also reduce lost days due to absence. TSI's Q-TRAK™ Indoor Air Quality Monitor 7575 provides quick, accurate information to assess key indoor air quality (IAQ) parameters.
Applications
- IAQ investigations
- Industrial hygiene surveys
- Baseline trending and screening
- Building commissioning
- Tracking down emissions to their source (point source location)
Technical Specification
| Carbon Monoxide (IAQ Probe Model 982) | Sensor Type - Electro-chemical
Range - 0 to 500 ppm
Accuracy - ±3% of reading or 3 ppm, whichever is greater
Resolution - 0.1 ppm
Response T |
|
| Carbon Dioxide (IAQ Probe Models 980 and 982) | Sensor Type - Dual-wavelength NDIR (non-dispersive infrared)
Range - 0 to 5,000 ppm
Accuracy6 - ±3.0% of reading or ±50 ppm, whichever is gr |
|
| Temperature (IAQ Probe Models 980 and 982) | Sensor Type - Thermistor
Range - 0 to 60°C (32 to 140°F)
Accuracy - 3 0.5°C (±1.0°F)
Resolution - 0.1°C (0.1°F)
Response Time - 30 seconds ( |
|
| Relative Humidity (IAQ Probe Models 980 and 982) | Sensor Type - Thin-film capacitive
Range - 5 to 95% RH
Accuracy4 - ±3% RH
Resolution - 0.1% RH
Response Time - 20 seconds (for 63% of final |
|
| % Outside Air | Range - 0 to 100%
Resolution - 0.1% |
|
| Barometric Pressure - Range | 517.15 to 930.87 mm Hg (20.36 to 36.648 in. Hg) |
|
| Barometric Pressure - Accuracy | ±2% of reading |
|
| Operating Temperature | 5 to 45°C (40 to 113°F) |
|
| Storage Temperature | -20 to 60°C (-4 to 146°F) |
|
| Logging Capability - Range | Logs up to 56,035 data points with key (4) measured
parameters enabled, 39 days at 1-minute log intervals |
|
| Time Constants | 1 sec, 5 sec, 10 sec, 20 sec, 30 sec (user selectable) |
|
| Log Intervals | 1 second up to 1 hour (user selectable) |
|
| Meter Dimensions | 9.7 cm × 21.1 cm × 5.3 cm (3.8 in. × 8.3 in. × 2.1 in.) |
|
Dimensions
| Title | (mm) | (inch) | (kg) | (lbs) |
|---|---|---|---|---|
| Probe Dimensions - Length | 178 | 7.0 | ||
| Probe Dimensions - Diameter | 19 | 0.75 | ||
| Weight - with Batteries | 0.36 | 0.8 |
-
TSI Q-TRAK 7575 Indoor Air Quality Monitor PDF brochure
Download a full PDF brochure of TSI Q-TRAK 7575 Indoor Air Quality Monitor page including the overview, specifications, applications and more.